Palaceside Building is conducting legally required indoor fire-hydrant inspection and hose pressure tests through September 27.

消火栓1.jpg

Many of you have seen hydrants like the photo at right by restroom entrances. There are 93 locations, two hoses each — 186 hoses. We cannot have no water or damaged hoses in an emergency, so checks never stop. Hydrants are inspected every six months; hoses must be replaced after ten years, or pressure-tested every three years if kept longer. Tests use dedicated equipment = photo top =, applying specified pressure (0.7 MPa) for five minutes to check for leaks.

We also completed six-month fire-extinguisher checks — over 400 in the building. We sample a set ratio for disassembly = photos below =: fix the body and open the lid, remove contents, adjust and reassemble — sweaty work in lingering summer sun.